Investigation of particulate matters of the university classroom in
Slovakia
Eva Kridlova Burdova^*, Silvia Vilcekovaa, Ludmila Meciarovaa
aInstitute of Environmental Engineering, Faculty of Civil Engineering, Vysokoskolska 4, 042 00 Kosice, Slovakia
Abstract
University students spend most of their time in classrooms that do not always represent an ideal environment for education. This is mainly due to the fact that most university buildings in Slovakia are old. Classrooms can be contaminated by various indoor pollutants, such as allergens, particles, volatile organic compounds etc. Indoor air pollution can lead to long-term and short-term health problems for students and staff but also can lead to decreasing productivity. It is therefore essential to deal with the monitoring of indoor environmental quality in universities in Slovakia and propose realizable measures to improve this situation. The aim of this study is to investigate the particulate matters. The measurements were carried out in the university classroom during lessons. These measurements were repeated during to lessons carried out once a week for the duration of one month. Handheld 3016 IAQ - device was used for determination of particulate matter concentrations. Air temperature and relative humidity was set with multifunction device Testo 435-4. Questionnaire survey based on subjective perception of indoor environmental quality was also performed during this study. Students fill in these questionnaires at the beginning and at the end of lessons. Analysis was used for investigation of occurrence of PM concentrations and subjective evaluation of students. © 2016 The Authors.PublishedbyElsevierLtd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.Org/licenses/by-nc-nd/4.0/).
Peer-review under responsibility of the organizing committee of the SBE16 Tallinn and Helsinki Conference. Keywords: particulate matter, indoor environmental quality, perceived air quality, classroom
1. Introduction
Indoor environment quality (IEQ) is considered as an indicator of the level of comfort which is not confined to the thermal conditions, it includes elements such as thermal comfort, acoustic comfort, indoor air quality and visual
* Corresponding author. Tel.:+421 55 602 4125. E-mail address: eva.kridlova.burdova@tuke.sk
1876-6102 © 2016 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
Peer-review under responsibility of the organizing committee of the SBE16 Tallinn and Helsinki Conference. doi:10.1016/j.egypro.2016.09.111
comfort [1]. Balancing energy performance and IEQ performance has become a conventional tradeoff in sustainable building design. In recognition of the impact IEQ performance has on the occupants of educational facilities, universities are increasingly interested in tracking the performance of their buildings [2]. Nearly zero emission or nearly zero energy buildings are main goals in various country roadmaps for 2020 [3]. Thanks to energy building certification, more Low energy buildings are being built with regard to this, we must point out that: a low energy building does not always correspond to high indoor comfort quality [4]. Exposure to particulate matters (PM) has been associated with higher rate of morbidity and mortality in urban areas and World Health Organization's International Agency for Research on Cancer (IARC) has classified PM component of air pollution as a carcinogen [5]. Pollution of the atmosphere continues to be a global concern for scientific research, environmental health and climate change. The control of air pollution over the past fifty years has seen the achievement of significant improvements in the quality of air, particularly in the urban environment [6]. Particulate matter is a key indicator of air pollution brought into the air by a variety of natural and human activities. As it can be suspended over long time and travel over long distances in the atmosphere, it can cause a wide range of diseases that lead to a significant reduction of human life. The size of particles has been directly linked to their potential for causing health problems. Small particles of concern include "inhalable coarse particles" with a diameter of 2.5 to 10 ^m and "fine particles" smaller than 2.5 ^m in diameter [7]. PM has well-known negative health effects on humans. PM exposure occurs mainly indoors because people spend most of their time inside buildings, especially in their homes [8]. Global climate change and increasing energy requirements have led to the development of energy-saving buildings typically characterized by low air-exchange rates. Given that people may spend more than 90% of their time in such enclosed spaces during the main activities of living, working and transportation, the investigation of indoor air quality (IAQ) in these micro-environments is of paramount importance [9]. High concentrations of air pollutants in ambient air may cause acute or chronic health effects, and even cause premature deaths in the elderly people and people with asthma; thus, the air quality forecasting studies became an important research topic for public health. A wide range of operational alert systems have been developed utilizing statistical and hybrid models, to take precautions before and during air pollution episodes [10]. Many studies deals with measure the indoor air quality in classroom. In study [11] was measure the indoor air quality in classrooms with special emphasis on particulate matter (PM10) and carbon dioxide (CO2) and the impact of cleaning and ventilation. Another study [12] reports particle mass and number concentrations and student exposure in classrooms in three secondary schools in Lublin, Poland, during the winter (February-March) and summer (May-June) season measurements. Research [13] was conducted at three selected schools in semiurban areas of Bandar Baru Bangi and Putrajaya, Malaysia to investigate the influence of the local surroundings on the IAQ in the school classrooms. The concentrations of gas pollutants (CO, CO2) and particulate matter (PM10, PM2.5 and PM!) have been determined using automatic portable indoor air spectrometers. The purpose of another study [14] was to measure and compare the indoor concentration levels of particulate matter (PM2.5 and PM10) in order to find out the spatial and seasonal variations across Gaza strip schools. Study [15] evaluated indoor PM concentrations on different microenvironments of three rural nursery schools and one urban nursery school, being the only study comparing urban and rural nursery schools considering the PM1, PM2.5 and PM10 fractions (measured continuously and in terms of mass). Outdoor PM2.5 and PM10 were also obtained and I/O ratios have been determined. Passive sampling methodology was applied in another study [16] to collection of PM in classrooms of urban and rural primary schools. The samples were taken during a year by passive deposition allowing the study of seasonal variability of the particles masses and chemical content. Another study [17] presents an assessment of schools' indoor environmental quality, based on investigations carried out in three Italian classrooms in Treviso, in the North-East of Italy. Portugal study [18] presents an alternative approach using different ventilation systems. This system was applied in a part of a school building and the indoor environment was monitored during two months. Studies have been showing strong associations between exposures to indoor PM and health effects on children [15]. This study aimed at investigating the particulate matters in university classroom. The measurements were carried out in the university classroom during lessons and repeated once a week for the duration of one month. Subjective perception by questionnaire survey of indoor environmental quality was also performed during this study.
2. Materials and Methods
The objective of this study was to determine the level of particulate matter concentration and air temperature and relative humidity in university one classroom. Five measurements were carried out during the lessons in March. Indoor environmental quality monitoring was carried out in the university classroom, which is located in the 4th floor of building of Faculty of Civil Engineering. The teaching was attended by 10 students plus teacher. 60% of students were women with mean weight of 55.6 kg and mean height of 169.8 m, and 40% were men with mean weight of 82.8 kg and with mean height of 182.3 m. 90% from respondents are non-smoker. Average age of students was 24 years. The selected classroom had capacity up to 38 persons and volume of 191 m3. The classroom was equipped with 19 desks from particleboard, 38 plastic chairs, blackboard for chalk, 8 computers, and one PC projector. In the classroom, there were 10 windows and 10 skylights, one door, lime plasters with water based paint on the walls, and flooring from OSB. All windows and doors have been open for 5 minutes before the lecture, and then they were closed and re-opened at the end of the lecture. No forced ventilation or air-conditioning system was used in the classroom. Measurement lasted 140 minutes. Concentrations of particulate matter were determined using HANDHELD 3016 laser particle counter. Air temperature and relative humidity were measured with multifunctional measuring device TESTO 435-4 with the IAQ probe. All measuring devices were placed in the centre of the classroom in the height of 1.1 m above the floor. Questionnaire survey was carried out in the classroom for the purpose of evaluation the influence of indoor environmental parameters on students, except the monitoring of IEQ parameters. The questionnaires were completed only by students at the beginning and the end of the lecture, but teacher was also present in the classroom during measurement. Different types of evaluation scales were used in the questionnaires. There were used scales of perception, scales of sensational evaluation (Fig. 1 a, b; Fig. 2 a), and overall evaluation for indoor environment (Fig. 2 b) [19].
How do you rate your therm al sensation?
-- Hot
-- Warm
- - Slightly warm
-- Neutral
-- Slightly cool
-- Cool
How do you perceive the temperature?
- Clearly acceptable
Just acceptable -p Just unacceptable
- -Clearly unacceptable
-L Cold
Fig. 1. (a) Thermal sensation; (b) Perceived temperature
Do you want the room temperature?
a) Higher
b) No change
c) Lower
How do you perceive the air quality?
Clearly acceptable
Just acceptable Just unacceptable
Cle axly unacceptable
Fig. 2. (a) Temperature; (b) Perceived air quality
3. Results
3.1. Objective measurement
The minimum and maximum air temperature and humidity measured in classroom are shown in the table (Table 1). The minimum temperature of 21°C (23.3.2016), maximum of 26.5°C (2.3.2016) and mean value of 23.99°C. The minimum air humidity in classroom ranged from 27.1 % (23.3.2016) to 38.1% (9.3.2016) with mean value of 32.57 %.
Table 1. Temperature and relative humidity
Date 2.3. 2016 9.3. 2016 16.3 .2016 23.3 .2016 30.3 .2016 Average
Min Max Min Max Min Max Min Max Min Max Min Max Mean
Temperature [°C] 22.9 26.5 22.9 25.7 22.4 25.6 21 26.4 22.4 25.5 21 26.5 24.13
Relative humidity [%] 30.7 38.1 33.3 38.1 27.5 35.4 27.1 34 30.8 33.8 27.1 38.1 32.88
Table 2. Mean values of particulate mass concentrations
0.3^m dif 0.5^m dif 1.0^m dif 2.5^m dif 5.0^m dif 10.0^m dif Total PM Day PM m3 PM m3 PM m3 PM m3 PM m3 PM m3 m3
2.3.2016 0.00 6.21 9.51 13.15 37.06 71.65 95.30
9.3.2016 0.00 4.97 7.08 9.81 29.54 64.26 89.08
16.3.2016 0.00 4.64 6.53 11.10 43.02 81.73 108.04
23.3.2016 0.00 6.38 9.56 14.43 49.84 95.50 121.32
30.3.2016 0.00 4.35 7.40 12.58 43.30 90.03 134.33
Min 0.00 4.35 6.53 9.81 29.54 64.26 89.08
Max 0.00 6.38 9.56 14.43 49.84 95.50 134.33
Mean 0.00 5.31 8.02 12.21 40.55 80.63 109.61
160 140
120 100 80 60 40 20 0
0.3^m dif 0.5^m dif 1.0^m dif2.5^m dif 5.0^m dif 10.0^m Total PM PM m3 PM m3 PM m3 PM m3 PM m3 dif PM m3 m3
2.3.2016 9.3.2016
16.3.2016 23.3.2016
30.3.2016
Fig. 3. Comparison of particulate mass concentrations.
Total PM concentrations presented as measured particles without size fraction selection differed widely and ranged from 89.08 to 134.33 ^g.m-3 in the monitored university classroom with an average value of 109.61 ^g.m-3. PM10 concentrations ranged from 64.26.0 to 95.5.4 ^g.m-3. The measured PM10 values were compared with the maximum value according to Slovak legislation (Decree of the Ministry of Health of the Slovak Republic No. 259/2008) [20]. The maximum permissible value for PM10 indoor concentration (50 ^g.m-3) was exceeded in each of measurements. The calculated average value of PM10 in the offices (80.63 ^g.m-3) was also found to be higher than the permissible limit. Comparison of the PM concentrations measured in the monitored classroom of the present study is illustrated in Figure 2. Values of mean mass concentrations of particulate matters for each measured fraction (PM0.3-0.5, PMi.Q.2.5, PM2.5-5.0, PM50-100) in classroom are presented in the Figures 4-7.
■2 3 2016 9 3 2016 16.3.2016 23 3 2016 30.3.2016
Fig. 4. Course of particulate number concentration of PM0.3-0.5.
Fig. 5. Course of particulate number concentration of PM10-25.
Fig. 6 Course of particulate number concentration of PM25_50.
PM5.0-10.0
>—————————————1^0
^—2.3.2016 ^—9.3.2016 ^—16.3.2016 ^—23.3.2016^—30.3.2016
Fig. 7 Course of particulate number concentration of PM50_100. 3.2. Subjective measurement
Results of questionnaire survey correspond to objective measurements in the classroom during to lessons carried out once a week for the duration of one month. Student's evaluated of indoor environmental quality parameters was worse at the end of the lecture as at the beginning. In average, students evaluated temperature as slight heat, humidity as neutral. Students marked the indoor environment as more acceptable than unacceptable and well tolerable in general. In the table (Table 3) is shown result from subjective evaluation on IEQ parameters. In average, 52% of student rated air temperate as comfort and 28% as slight discomfort at the beginning of the lecture. On the other hand, 30.5% of students rated air temperature as comfort, 64.2% as slight discomfort, and 5.3% as discomfort at the end of lecture. 94.7% of students evaluated level of humidity as comfort, 2.5% as slight discomfort and 2.8% as discomfort at the beginning of lecture, and 67.6% as comfort and 32.4% as slight discomfort at the end of lecture.
These results correspond to objective measurements in the classroom. Students marked the indoor environment as more acceptable than unacceptable and well tolerable in general.
Table 3. Result from subjective evaluation of IEQ parameters
Parameter 2.3.2016 9.3.2016 16.3.2016 23.3.2016 30.3.2016 Mean
the beginning 0.7 1.1 0.5 0.89 0.8 0.798
Temperature the end 1.4 1.3 1.1 1.22 1.2 1.244
the beginning 0.2 0.1 0.1 0 0 0
Humidity the end 0.3 0 0.1 0 0 0
the beginning 0.5 0.14 0.25 0.44 0.8 0.426
IEQ the end 0.7 0.57 0.88 0.89 0.4 0.688
4. Discussion
Particles are produced by photochemical atmospheric reactions and the coagulation of combustion products from automobiles and stationary sources, with lifetimes of several days or more. The occurrence of particulate matters indoors depends on outdoor pollution and its transport indoors as well as on the presence of indoor sources [21]. Our previous study [22] were investigated in terms of the particulate matter occurrence in selected office room. Both mass and number concentrations have been measured with the result: much higher mass concentrations have been observed in room 2 (out of operation) when compared to room 1 (operational mode) for all size fractions; the ratio of mass concentrations for room 2/room 1 ranged from 1.15 for PM10 to 2.45 for PM0.5; PM10 concentrations of particulate matters measured in office rooms (27.9 and 32.2 ^g.m-3) did not exceed the Slovak limit value for indoor air (50 ^g.m-3). Another previous study [23] was focused at investigation of indoor environmental quality, performance and comfort of employers in selected office building. Study was conducted during the heating and non-heating season. Occupants were requested to evaluate their subjective and objective performance. The average overall performance of users in the heating season was 84.4% and in the non-heating season was 98.3%. The measured PM10 values in our study were compared with the maximum value according to Slovak legislation that lead the maximum permissible value for PM10 indoor concentration (50 ^g.m-3). This permissible value was exceeded in each of measurements. Measurement of particulate matter concentrations were also performed in study [14]. In this study were co carried out using hand held particulate matter instrument during fall, winter and spring seasons from October 2011 to May 2012 inside and outside the classrooms of twelve naturally ventilated schools located in Gaza strip, Palestine. The average concentration of indoor PM10 was 349.49 (+/-196.57) mg/m3 and for PM2 5 was 103.96 (+/-84.96) mg/m3. Another study was oriented to measure the indoor air quality in classrooms with special emphasis on particulate matter (PM10) and the impact of cleaning and ventilation with the result: levels of PM10 in the classrooms during the 3 weeks were 69719 mg/m3 and they were dominated by occupancy and the persons' activity. Intensified cleaning showed a significant decrease in all classrooms (79722 to 64715 mg/m3). The effect of ventilation on levels of PM10 was inconsistent. Result of study from [13] show that the overall average concentrations of the main parameters recorded inside the schools were 31 mg/m3 (PM10), 18 mg/m3 (PM2.5) and 16 mg /m3 (PMi). These concentrations were below the recommended values suggested in Malaysia.
5. Conclusion
Monitoring of classroom in our study during to lessons shows that PM mass concentrations ranged widely based on particle size: 64.26-95.50 ^g/m3, 29.54-49.84 ^g/m3, 9.81-14.43 ^g/m3, 4.35-6.38 ^g/m3, 0 ^g.m-3 for PM10, PM5, PM2 5, PM1, and PM0.5, respectively. The permissible value for PM10 indoor concentration (50 ^g/m3) was exceeded in 100 % of measurements. Results of objective measurement correspond to subjective measurements in the classroom. Students marked the indoor environment as more acceptable than unacceptable and well tolerable in general. Increased levels of PM10 concentrations measured indoor as well outdoor resulted in heating of houses with solid fuel. Use of renewable energy sources seems a better alternative in terms of air pollution especially in the heating season. Reducing the concentrations of particulates in the air during the possible construction works which
can potentially increase the concentration it would be achieved by sprinkling the transported building materials and components or their covering with a sheet.
The future work will be aimed on monitoring a statistically significant set of selected university classrooms, determination of indoor PM occurrence depending on the surrounding environment, identification of indoor sources of PM and determination of correlation between subjective perception and measured PM concentration.
Acknowledgements
This paper was financially supported by the Slovak Grant No. 1/0307/16 and No. 1/0481/13. References
[1] Mihai T, Iordache V, Determining the indoor environment quality for an educational building. Energy Procedia 2016;85:566-574.
[2] Asmar ME, Chokor A, Srour I, Are Building Occupants Satisfied with Indoor Environmental Quality of Higher Education Facilities? Energy procedia 2014;50:751-760.
[3] Erhorn-Kluttig H, Erhorn H, School of the Future - Towards zero emission with high performance indoor environment. Energy Procedia 2014;48:1468-1473.
[4] Fabbri K, Tronchin L, Indoor environmental quality in low energy buildings. Energy Procedia 2015;78:2778-2783.
[5] Li H, Fang CHY, Shi W, Gurusamy S, Li S, Krishnan MN, George S, Size and site dependent biological hazard potential of particulate matters collected from different heights at the vicinity of a building construction. Toxicology Letters 2015;238:20-29.
[6] McNabola A O'Luanaigh N, Gallagher J, Gill L, The development and assessment of an aspiration efficiency reducing system of air pollution control for particulate matter in building ventilation systems. Energy Build 2013;61:177-184
[7] Kim K, Kabir E, Kabir S, A review on the human health impact of airborne particulate matter. Environ International 2015;74:136-143.
[8] Urso P, Cattaneo A, Garramore G, Peruzzo C, Cavallo DM, Carrer P, Identification of particulate matter determinants in residential homes. Build Environ 2015;86:61-69.
[9] Szigeti T, Kertesz Z, Dunster C, Kelly FJ, Zaray G, Mihucz VG, Exposure to PM2.5 in modern office buildings through elemental characterization and oxidative potential. Atmospheric Environment 2014;94:44-52.
[10] Ta§pinar F, Bozkurt Z, Application of artificial neural networks and regression models in the prediction of daily maximum PM10 concentration in Dduzce, Turkey. Fresenius Environmental Bulletin 2014;23(10):2450-2459.
[11] Heudor U, Neitzert V, Spark J, Particulate matter and carbon dioxide in classrooms - The impact of cleaning and ventilation. Int. J. Hyg. Environ. Health 2009;212:45-55.
[12] Polednik B, Particulate matter and student exposure in school classrooms in Lublin, Poland. Environmental Research 2014;12:134-139.
[13] Razali NYY, Latif MT, Dominick D, Mohamad N, Sulaiman FR, Srithawirat T, Concentration of particulate matter, CO and CO2 in selected schools in Malaysia. Building and Environment 2015;87:108-116.
[14] Elbayoumi M, Ramli NA, Yusof NFFM, Al Madhoun W, Spatial and seasonal variation of particulate matter (PM10 and PM2.5) in Middle Eastern classrooms. Atmospheric Environment 2013;80:389-397.
[15] Nunes RAO, Branco PTBS, Alvin-Ferraz MCM, Martins FG, Sousa SIV, Particulate matter in rural and urban nursery schools in Portugal. Environmental Pollution 2015;202:7-16.
[16] Canha N, ALmeida SM, Freitas MC, Trancoso M, Sousa A, Mouro F, Wolterbeek HTn, Particulate matter analysis in indoor environments of urban and rural primary schools using passive sampling methodology. Atmospheric Environment 2014;83:21-34.
[17] Pistore L, Cappelletti F, Romagnoni P, Zonta A, Assessment of the IEQ in two high schools by means of monitoring, surveys and dynamic simulation. Energy procedia 2015;82:519-525.
[18] Almeida RMSF, Freitas VP, IEQ assessment of classrooms with an optimized demand controlled ventilation system. Energy procedia 2015;78:3132-3137.
[19] STN EN 15251 Indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality, thermal environment, lighting and acoustics
[20] Decree of the Ministry of Health of the Slovak Republic No. 259/2008
[21] Vilcekova S, Kubinova J, Kridlova Burdova E, Measuring of Outdoor and Indoor Particulate Matter Concentrations in Village of Jasov, Solid State Phenomena 2016;244:182-187.
[22] Vilcekova S, Estokova A, Kridlova Burdova E Occurrence of particulate matters concentrations in office spaces. Protection and Restoration of the Environment : 12th International Conference : Proceedings: Skiathos Island, June 29 - July 3, 2014. Thessaloniki: Grafima Publ., 2014;1208-1213.
[23] Vilcekova S, Kridlova Burdova E, Budaiova Z, Indoor Environmental Quality and Performance in Office Buildings. Sustainable Built Environment 2016, Dubai : The British University in Dubai, 1-7.